You have probably had this one. The fridge runs perfectly in the driveway, then throws a tantrum on the second day in the bush and starts cutting out overnight. The battery tests fine. The fridge tested fine at home. So what changed?
The cable. Specifically, the cable is too thin for the distance it has to carry current. It is the most common fault in DIY 12V touring setups and the least obvious, because nothing looks broken.
The Short Version
- Aim for less than 3% voltage drop, about 0.36 V on a 12 V system, measured at the load while it is running.
- Cable length counts twice: current has to travel out and come back.
- If the fridge is cutting out, suspect the cable and the connections before you suspect the battery.
- Measure at the appliance's terminals under load, not at the battery with everything switched off.
What Voltage Drop Actually Is
Every cable resists current a little. Push current through a long, thin cable and some of your 12 volts goes into heating the copper instead of running the fridge. The longer the run and the thinner the cable, the more you lose.
Twelve volts gives you very little headroom to play with. Three percent of 12 V is 0.36 V. Where it bites is at the fridge: many units have a low-voltage cutout that trips somewhere around 11 V at their own terminals. That protection exists to stop you wrecking the battery, but it cannot tell the difference between a battery that is genuinely flat and a cable that is stealing a volt on the way through. So the fridge shuts down, the compressor rests, the voltage recovers, and it starts again. That is the clicking you hear at 2am.
Sizing the Cable: The Working Numbers
Voltage drop is calculated over the round trip, out to the load and back again. The formula is straightforward enough: drop equals two times the one-way length, times current, times the resistivity of copper, divided by the cable's cross-sectional area. You do not need to sit down with a calculator, though, because the practical answer is nearly always to go one size heavier than you first thought.
The table below gives approximate maximum one-way cable runs for copper cable at typical under-bonnet temperatures, sized to stay under the 3% target. Treat these as a starting point with margin built in, and not as a manufacturer's rating.
| Cable size | 5 A load | 10 A load | 20 A load |
|---|---|---|---|
| 4 mm² | about 7 m | about 3.8 m | about 1.9 m |
| 6 mm² | about 11 m | about 5.8 m | about 2.9 m |
| 8 mm² | about 15 m | about 7.8 m | about 3.9 m |
| 16 mm² | about 31 m | about 15 m | about 7.8 m |
The pattern is the useful part. Doubling the current halves the distance you can run. Doubling the cable area doubles it. That is why the answer to a marginal 12 V run is nearly always heavier cable rather than a bigger battery.
The Return Path Is Half the Circuit
This is where a lot of installs come undone. The positive cable gets all the attention and the return is left to the vehicle's chassis. An earth through a rusty bolt, a painted seam or a short length of thin wire can add more resistance than the positive run ever did.
Run a dedicated negative cable back to the battery or to a solid busbar. If you must earth to the chassis, use a star washer on bare metal, seal it afterwards, and check the drop across that joint as its own item.
And Then There Are the Connections
A perfect cable with a bad crimp is still a bad circuit. Voltage drop hides in joints: a lug crimped with the wrong die, a terminal that has been wet, a plug with small contacts. Plugs deserve particular suspicion, because a tired 12-pin trailer plug can lose meaningful voltage across its own contacts before the current has travelled a single metre of cable.
- Crimp with the correct die for the lug, then seal with adhesive-lined heat-shrink.
- Use lugs sized to the cable, not the smallest that will fit over the stud.
- Keep every connection clean and dry, and re-check the ones you can reach.
- If a joint is warm after ten minutes of running, it is costing you voltage.
How to Measure Yours
Turn the load on, let it run for a minute, then measure the voltage at the battery terminals and again at the appliance's terminals. The difference is your total drop, including every joint and both cable runs. Do it under load, because a reading with everything switched off tells you nothing.
If you are seeing close to a volt, that is the whole mystery explained. Fix the cable, the return path and the connections before spending anything on a new battery.
Real-World Tips
- Size for your worst case, not your average. Compressor start-up current is far higher than the running figure.
- Buy cable once. Going a size heavier costs a little more and behaves far better in the heat.
- Label both ends of every run while you are building it. Future you will be grateful.
- Fuse the positive as close to the battery as practical, and carry spares.
- Check the drop again after a season of corrugations. Vibration loosens what corrosion has not already reached.
Doing the Job Properly
If you are running new circuits for a fridge, a charger or a compressor, the hardware matters as much as the arithmetic: sealed connectors, correctly sized lugs, and cable rated for the temperature it will actually live in. Our 12V accessories range covers the terminals, cable and connections that sit between the battery and the load.
Over to You
Voltage drop is one of those problems that feels mysterious until you measure it, and obvious afterwards. Get the cable right and a lot of "faulty fridge" stories turn out to be nothing of the sort. If you have chased one down yourself, tell us what you found in the comments.
Leave a comment (all fields required)